Part B fire-escape windows and Part F trickle vents

Under Irish TGD Part B, upstairs habitable rooms need a fire-escape opening of at least 0.33 m² clear area (minimum 450 mm wide and high, sill 800 mm to 1100 mm off the floor). Under TGD Part F, airtight replacement windows need background trickle vents unless mechanical ventilation serves the room.

The two Irish Building Regulations most often missed on cheap replacement quotes, and how to verify compliance before manufacturing.

Free, no obligation. One local installer prices it, not five.

  • ≥ 0.33 m²Part B clear escape area
  • ≥ 450 mmminimum clear width and height
  • 800–1100 mmpermitted internal sill height
  • 2,500 mm²typical habitable vent EQA
Dark-framed tilt-and-turn window with lever handles facing wintry trees outside

Part B fire-escape (egress) dimensions explained

When replacing older windows, you must never leave fire escape worse than before, and every upstairs bedroom or attic room without a protected escape door needs a compliant escape sash. Watch the arithmetic trap: a 450 mm × 450 mm gap equals only 0.20 m², well short of the 0.33 m² statutory minimum. If clear width is 450 mm, clear height must be at least 735 mm (or 550 mm × 600 mm).

  1. Clear unobstructed area ≥ 0.33 m². Measured inside the open sash and frame projection, not the brickwork hole outside.
  2. Neither dimension under 450 mm. Both clear open width and clear open height must reach at least 450 mm.
  3. Internal sill 800 mm to 1100 mm above floor. Too high stops occupants climbing out; below 800 mm requires guarding or toughened glazing under Part K.
  4. Egress hinges and easy-clean release. Side-hung fire-escape hinges swing wide to 90 degrees immediately; avoid placing child restrictors that cannot be released swiftly without a hidden key.

Price my openings

Four quick taps and our Irish price range shows before any contact detail is asked for. One local installer rings you, not five.

Replacement windows, 8 to 12 openings (3-bed semi size), in uPVC: €4,800 to €7,800, supplied and fitted before any SEAI grant.

Step 1 of 5

What are you replacing or building?

Pick the closest match. The surveyor checks every opening in person.

How this package estimate is worked out

The range reflects typical supply-and-fit door and window prices in Ireland for that package type, opening count and frame material, assuming existing structural openings and standard removal of old frames. Triple glazing typically adds 10% to 15%, coloured uPVC foil adds 15% to 20%, and widening a rear wall for a wide slider or bifold requires a structural lintel priced separately. Ask for written U-values and 13.5% VAT confirmation. Use this range to budget: only an on-site survey gives a fixed price.

Part F background ventilation: why trickle vents stop mould

Old 1980s timber and metal windows leaked air around every sash, accidentally ventilating bedrooms and kitchens. Fitting tight new triple-seal frames closes those gaps overnight. Without planned airflow under Technical Guidance Document F (2019), indoor humidity climbs quickly and causes mould behind wardrobes and condensation on cold corners.

Natural ventilation (existing home)

Trickle vent requirement
Background vents required in habitable rooms
Practical note
Match or improve existing wall/window vents; keep extractor fans running in baths and kitchens.

Continuous extract (cMEV / DCV)

Trickle vent requirement
Typically ≥ 2,500 mm² EQA per room
Practical note
Over-frame or acoustic slot vents supply steady fresh air without howling draughts.

Whole-house heat recovery (MVHR)

Trickle vent requirement
Trickle vents omitted
Practical note
New builds and deep retrofits with balanced MVHR keep frames sealed for airtightness.

Common questions before you order

Can top-hung windows count as bedroom fire-escape windows?

Usually no unless the clear opening below the sash meets 0.33 m² and 450 mm clear height easily. Side-hung egress casements or inward tilt-and-turn sashes are the standard Irish solution.

Do trickle vents ruin my window U-value or let traffic noise in?

Standard slot vents add a small local chill in gales. On busy roads or exposed coastal homes, specify acoustic trickle vents or wall-mounted insulated vents instead of cutting holes through slim frames.

What if my existing bedroom sill is lower than 800 mm?

Glazing within 800 mm of the finished floor level (and within 300 mm of a door) must use toughened or laminated safety glass under Part K to prevent impact injury.

Will an installer check egress rules during the survey?

Yes. Ask the surveyor to mark 'egress' explicitly beside every upstairs bedroom item on the written opening schedule before signing off.